What is DGA Monitoring?
DGA (dissolved gas analysis) monitoring measures the gases dissolved in a transformer’s insulating oil to detect developing internal faults. Faults such as partial discharge, arcing, and overheating break down the oil and paper insulation, producing specific gases. Online DGA monitoring tracks these gases continuously, providing early warning between periodic oil samples.
Each fault type produces a characteristic gas signature. Hydrogen indicates partial discharge, acetylene indicates arcing, ethylene indicates high-temperature thermal faults, and carbon monoxide and carbon dioxide indicate degradation of cellulose (paper) insulation. Engineers interpret these gas levels and their rates of change using methods described in IEEE C57.104 and IEC 60599, such as the Duval triangle and Rogers ratios.

Why Should I Implement DGA Monitoring On My Power Transformer?
Dissolved gas is a leading indicator of the health of a transformer. Dissolved gas analysis (DGA) helps determine the types of abnormal events that may be occurring within the main tank. Therefore, it is an effective way to analyze partial discharge, arcing, excessive thermal conditions and more.
DGA testing is typically performed annually to determine the levels of gas dissolved in the oil. However, faults can develop and escalate between sampling intervals. CIGRE’s international Transformer Reliability Survey (Technical Brochure 642), covering 964 major failures across 58 utilities in 21 countries, found that windings, tap changers, and bushings account for most major transformer failures, and many of these fault types generate dissolved gases as they develop. Online DGA monitoring provides a continuous look at the gases in the main tank, so changes are caught as they happen rather than at the next scheduled sample.
What is Key Gas Monitoring?
Key gas monitoring is a cost effective solution that allows monitoring to be implemented more widely across the entire fleet. It’s an effective method that detects hydrogen generation levels inside a transformer’s main tank. Hydrogen generation occurs when thermal levels are above a transformer’s normal operating temperature. Therefore, monitoring for key gas components provides an early indication of most abnormal operating conditions that may occur in the main tank.
Advantages of Key Gas Monitoring
Hydrogen is effective at providing an early indication of incipient faults, thereby reducing the chances of a transformer failing without some advance warning. Key gas monitoring, when used in conjunction with a good maintenance program consisting of routine DGA sampling and electrical testing, offers a dependable, cost-effective alternative to multi-gas monitoring. However, Hydrogen gas alone doesn’t provide enough data to perform a diagnosis as to the type of fault which is occurring.
DOWNLOAD THE KEY GAS MONITOR COMPARISON CHART
Download our handy comparison guide of key gas monitors available on the market today.
Types of Key Gas Monitors
Solid State-Palladium Based Sensor
- Sensor is self-calibrating
- Sensor is most commonly used in multi-gas sensors
- Sensor measures hydrogen only
Fuel Cell Sensor
- Sensor usually provides a composite measurement of hydrogen, acetylene, ethylene, and carbon monoxide
- Sensor uses a membrane to diffuse gases from the oil for measurement
- Sensor may require periodic calibration
Dynamic Ratings' B100 Electronic Temperature Monitor with Hydrogen

The B100 ETM is an analog gauge replacement that provides accurate indication of problems inside the transformer via fault gas detection. Add on the optional hydrogen sensor for an all-in-one, low cost solution that provides remote notification of any problems detected.
What is the Difference Between Key Gas and Multi-Gas Monitoring?
Key gas monitoring provides low-cost early warning across a whole fleet, while multi-gas monitoring identifies the type of fault on critical transformers. A key gas monitor focuses primarily on hydrogen to determine abnormal conditions within a transformer whereas multi-gas monitors can include hydrocarbons, carbon oxides, oxygen and nitrogen, allowing for an analytical assessment of transformer condition. The table below compares the two approaches.
| Feature | Key gas monitoring | Multi-gas monitoring |
|---|---|---|
| Gases measured | Hydrogen only (palladium sensors), or a composite reading of hydrogen, acetylene, ethylene, and carbon monoxide (fuel cell sensors) | Five, seven, or nine individual gases, depending on the monitor |
| Fault diagnosis | Gives early warning of an incipient fault but cannot identify the fault type on its own | Identifies the fault type (partial discharge, arcing, or thermal) using methods such as the Duval triangle and pentagon, Rogers ratios, and Doernenburg ratios |
| Maintenance | Palladium sensors are self-calibrating; fuel cell sensors may need periodic calibration | Requires periodic maintenance; gas chromatograph models also need carrier and calibration gas |
| Service life | Typically longer | Typically shorter than key gas monitors |
| Cost | Lower, which makes fleet-wide deployment practical | Higher, so usually reserved for the most important assets |
| Best suited for | Broad coverage across a transformer fleet, alongside routine lab DGA sampling and electrical testing | Critical transformers, heavily loaded transformers, transformers with fluctuating loads, and transformers that are frequently switched in and out of service |
What is Multi-Gas Monitoring?
Multi-gas offers advantages over key gas monitoring for critical transformers, transformers subjected to heavy loading, load fluctuation, and transformers that are regularly switched in and out of service. Multi-gas monitoring continuously provides a detailed analysis of a transformer’s condition.

Advantages of Multi-Gas Monitoring
Multi-gas monitoring allows you to extend routine maintenance and provides a quick assessment of the transformer’s condition. Therefore, Multi-gas monitoring is ideal for critical transformers. However, Multi-gas monitors can require periodic maintenance and typically have a shorter life span than key gas monitors.
Types of Multi-Gas Monitors
5 Gas Monitor
- Monitor typically looks at hydrogen, methane, ethane, ethylene and acetylene (combustible gases)
- Monitor allows for online diagnosis of fault gases (Duval’s triangle and pentagon, Doernenburg ratio, Rogers ratio and Stenestam’s ratio for analysis of LTC and OCB DGA)
7 Gas Monitor
- Monitor includes combustible gases as well as carbon monoxide and carbon dioxide
- Monitor provides the ability to analyze fault type as well as levels of carbon dioxide and carbon monoxide. This is useful for identifying degradation of solid insulation systems through trending of carbon oxide ratios and carbon monoxide levels
9 Gas Monitor
- Monitor provides the ability to identify fault type (arcing, thermal, partial discharge)
- 9 gas monitor includes oxygen and nitrogen levels which is useful for identifying exposure to atmosphere
What Each Dissolved Gas Indicates
Each type of transformer fault breaks down oil or paper insulation in a characteristic way, producing a recognizable pattern of gases. Engineers interpret these patterns using the methods described in IEEE C57.104 and IEC 60599.
| Gas | Primary indication | Measured by |
|---|---|---|
| Hydrogen (H2) | Partial discharge. Hydrogen is also produced by most other faults, which makes it a useful general early-warning gas. | Key gas, 5-, 7-, and 9-gas monitors |
| Methane (CH4) | Low-temperature overheating of oil and partial discharge | 5-, 7-, and 9-gas monitors |
| Ethane (C2H6) | Low- to medium-temperature overheating of oil | 5-, 7-, and 9-gas monitors |
| Ethylene (C2H4) | High-temperature overheating of oil | 5-, 7-, and 9-gas monitors |
| Acetylene (C2H2) | Arcing and other high-energy discharges. Even small amounts warrant prompt investigation. | 5-, 7-, and 9-gas monitors |
| Carbon monoxide (CO) | Overheating or degradation of cellulose (paper) insulation | 7- and 9-gas monitors |
| Carbon dioxide (CO2) | Aging and oxidation of cellulose insulation. The CO2/CO ratio helps assess paper condition. | 7- and 9-gas monitors |
| Oxygen (O2) and nitrogen (N2) | Not fault gases. Their levels show whether the oil is exposed to the atmosphere, such as through a seal leak or a problem with the oil preservation system. | 9-gas monitors |
DOWNLOAD THE MULTI-GAS MONITOR COMPARISON CHART
Download our handy comparison guide of multi-gas monitors available on the market today.
Methods for Measuring Multi-Gas DGA
Gas Chromatograph
- This method requires helium carrier and calibration gas consumables
- This method requires periodic maintenance
- Auto calibrating for this method is based on National Institute of Standards and Technology
- This method has a high level of accuracy
IR (Infrared)
- This method uses infrared frequency to measure extract gas
- This method requires inclusion of other technologies, as not all gases have an IR signature
- No consumables required for this method
- This method is sensitive to interfering gases
PAS (Photo Acoustic Spectroscopy)
- No consumables required for this method.
- This method can measure very low gas levels
- This method is sensitive to interfering gases
- This method uses photoacoustic detection to detect gas levels
DGA Monitoring Frequently Asked Questions
How often should transformer oil be tested for DGA?
Oil should be tested at least once a year with twice being preferable. With online monitoring, oil can be tested daily which greatly increases the chance of catching internal problems in their inception.
Which standards govern DGA interpretation?
IEEE C57.104 and IEC 60599 provide standards for DGA analysis.
One Monitoring System for All Your Transformer Data

Dynamic Ratings transformer monitors integrate with most third-party multi-gas DGA units, so you don’t have to replace the DGA equipment you already trust. We collect your DGA readings alongside temperature, bushing, tap changer, and other transformer data, then deliver it all in one view. With turnkey services for most DGA monitors, from installation and commissioning to ongoing support, you have a single partner accountable for your entire monitoring system.