DGA Comparison Chart: Multi Gas - Dynamic Ratings

DGA Comparison Chart: Multi Gas

How industry leading Dissolved Gas Analysis (DGA) monitors compare on gases monitored, diagnostic tools, installation and maintenance, and system specifications. Dynamic Ratings supports communication to all major DGA monitors. We recognize that DGA monitors have different advantages and no one product would be optimal for all customers.

Download PDF

Compare monitors

Select two or more monitors to compare them side by side. All monitors are shown until you make a selection.Showing only the monitors you selected.

SupportedBlank: not supported or not listed

DGA comparison chart, multi gas
FeatureDobleCalisto 5DobleCalisto 9DobleCalisto R9VaisalaOPT100 Optimus™General ElectricKelman TransfixServeronTM8MTE Meter Test EquipmentHydrocal 1005MTE Meter Test EquipmentHydrocal 1008MTE Meter Test EquipmentHydrocal 1009CamlinTotus G5CamlinTotus G9HitachiCoreSense M10
Gases monitored
Hydrogen H2YesYesYesYesYesYesYesYesYesYesYesYes
Methane CH4YesYesYesYesYesYesNoYesYesYesYesYes
Acetylene C2H2YesYesYesYesYesYesYesYesYesYesYesYes
Ethylene C2H4YesYesYesYesYesYesYesYesYesYesYesYes
Ethane C2H6NoYesYesYesYesYesNoYesYesNoYesYes
Carbon monoxide COYesYesYesYesYesYesYesYesYesYesYesYes
Carbon dioxide CO2NoYesYesYesYesYesNoYesYesNoYesYes
Nitrogen N2NoYesYesNoYes1YesNoNoNoNoYes1No
Oxygen O2NoYesYesNoYesYesNoNoYesNoYesNo
Other information
MoistureYesYesYesYesYesYesYesYesYesYesYesYes
Fluid compatibilityMineral oil, silicone and natural & synthetic estersMineral oil, silicone and natural & synthetic estersMineral oil, silicone and natural & synthetic estersMineral oilMineral oil and natural estersMineral oilMineral oil and synthetic estersMineral oil and synthetic estersMineral oil and synthetic estersMineral oilMineral oil, silicone and natural & synthetic estersMineral oil, silicone and natural & synthetic esters
Diagnostic tools through Dynamic Ratings hardware: gases
Duval 1YesYesYesYesYesYesNoYesYesYesYesYes
Duval 3a siliconeYesYesYesNoNoNoNoYesYesNoYesYes
Duval 3b FR3YesYesYesNoYesNoNoNoNoNoYesYes
Duval 3c MidelYesYesYesNoNoNoNoYesYesNoYesYes
Duval 3d BioTempYesYesYesNoYesNoNoNoNoNoYesNo
Duval 4 low tempYesYesYesYesYesYesYesYesYesNoYesYes
Duval 5 high tempYesYesYesYesYesYesYesYesYesNoYesYes
Duval 6 FR3 low tempYesYesYesNoYesNoNoYesYesNoYesYes
Duval 7 FR3 low tempYesYesYesNoYesNoNoYesYesNoYesYes
Duval Pentagon 1YesYesYesYesYesYesNoYesYesNoYesYes
Duval Pentagon 2YesYesYesYesYesYesNoYesYesNoYesYes
IEEE conditionsYesYesYesYesYesYesYesYesYesNoYesYes
Diagnostic tools through Dynamic Ratings hardware: ratios
IEC transformerYesYesYesYesYesYesYesYesYesNoYesYes
Rogers IEEEYesYesYesYesYesYesNoYesYesNoYesYes
DoernenburgYesYesYesYesYesYesNoYesYesNoYesYes
CO2/COYesYesYesYesYesYesNoYesYesNoYesYes
C2H4/C2H2YesYesYesYesYesYesYesYesYesNoYesYes
IEEE key gasYesYesYesYesYesYesYesYesYesNoYesYes
Duval 2 OLTC type IYesYesYesYesYesYesNoYesYesNoYesYes
Duval 2a OLTC type IIaYesYesYesYesYesYesNoYesYesNoYesYes
Duval 2b OLTC type IIbYesYesYesYesYesYesNoYesYesNoYesYes
Duval 2c OLTC type IIcYesYesYesYesYesYesNoYesYesNoYesYes
Duval 2d OLTC type IIdYesYesYesYesYesYesNoYesYesNoYesYes
Duval 2e OLTC type IIeYesYesYesYesYesYesNoYesYesNoYesYes
OLTC heating gasYesYesYesYesYesYesNoYesYesNoYesYes
Additional advantages when used with Dynamic Ratings
Dynamic Ratings certified to install and serviceYesYesYesYesNoNoNoNoNoNoNoNo
Single point support from Dynamic RatingsAvailableAvailableAvailableAvailableNoNoNoNoNoNoNoNo
Installation and maintenance
ConsumablesCalibration & carrier gasCalibration & carrier gasNo consumablesNo consumables, no maintenanceNo consumablesCalibration & carrier gasNo consumablesNo consumablesNo consumablesNo consumablesNo consumablesNo consumables
Recommended maintenance timelineVisual inspection every 12 months. Carrier gas and calibration gas replacement every 48 monthsVisual inspection every 12 months. Carrier gas and calibration gas replacement every 48 monthsVisual inspection every 12 monthsNo regular maintenance required; expected operating life >15 years5 years or 50,000 measurementsNot availableNot requiredNot requiredNot requiredMinor maintenance at 5 years, major maintenance at 10 yearsMinor maintenance at 5 years, major maintenance at 10 years10 years
Warranty30 months from shipping date30 months from shipping date30 months from shipping date24 months18 months18 months from shipment or 12 months24 months24 months24 monthsNot availableNot available36 months
Installation mounting (length × width × depth)489 × 502 × 337 mm (19 × 19.8 × 13.3 in), 35 kg (75 lb), stainless steel enclosure, connected to separate inlet and outlet transformer valves489 × 502 × 337 mm (19 × 19.8 × 13.3 in), 35 kg (75 lb), stainless steel enclosure, connected to separate inlet and outlet transformer valves721 × 670 × 343 mm (28.4 × 26.26 × 13.5 in), 57 kg (125 lb), painted SS, NEMA 4X, IP661630 × 675 × 453 mm (64 × 27 × 18 in), NEMA 4 IP66 enclosure900 × 600 × 389 mm (35 × 24 × 15 in), 90 kg (198 lb)559 × 508 × 284 mm (22 × 20 × 11.2 in), 29.5 kg (65 lb), NEMA 4X IP66 enclosure263 × 263 × 328 mm (10.4 × 10.4 × 12.9 in), fits on 1.5 in bore ball or gate valve with NPT or ISO 228 thread263 × 263 × 328 mm (10.4 × 10.4 × 12.9 in), fits on 1.5 in bore ball or gate valve with NPT or ISO 228 thread263 × 263 × 328 mm (10.4 × 10.4 × 12.9 in), fits on 1.5 in bore ball or gate valve with NPT or ISO 228 thread730 × 853 × 398 mm (28.7 × 33.6 × 15.7 in), 54 kg (119 lb), IP56 enclosure730 × 853 × 398 mm (28.7 × 33.6 × 15.7 in), 54 kg (119 lb), IP56 enclosureMeasurement head 392 × 264 × 158 mm, NEMA 4X IP67
System description
Type of technologyGas chromatographyGas chromatographyDifferential photoacoustic spectroscopy, TCD for H2, fluorescent dye sensor for O2, pressure sensor for N2, capacitive H2O sensorPatented optical NDIR spectral scanning sensors. Solid state hydrogen and moisture sensors immersed directly in oil flow.Photo-acoustic spectroscopy + solid state sensors for H2 and O2Gas chromatographyOptical NIR spectroscopy + solid state sensor for H2Optical NIR spectroscopy + solid state sensor for H2Optical NIR spectroscopy + solid state sensor for H2NDIR + solid state sensors for H2Photo-acoustic spectroscopy (PAS) + solid state sensors for H2 and O2Fourier transform mid-infrared spectroscopy (FTIR) + solid state sensors for hydrogen and moisture
Calibration verificationUses NIST traceable gas standard, once per dayUses NIST traceable gas standard, once per dayAutocalibration using water vaporPatented autocalibration reference cycleUses ambient airUses NIST traceable gas standardDGA adjustment toolDGA adjustment toolDGA adjustment toolPermanent calibration at factory. Calibrated verification gas check kitPermanent calibration at factory. Calibrated verification gas check kitPermanently calibrated at factory. Integrated frequency standard.
Accuracy2H2: ±(LDL+2%)
CO: ±(LDL+2%)
CH4: ±(LDL+2%)
C2H2: ±(LDL+2%)
C2H4: ±(LDL+2%)
H2O: ±2 ppm
H2: ±(LDL+2%)
CO: ±(LDL+2%)
CO2: ±(LDL+2%)
CH4: ±(LDL+2%)
C2H2: ±(LDL+2%)
C2H4: ±(LDL+2%)
C2H6: ±(LDL+2%)
O2: ±(LDL+2%)
N2: ±(LDL+2%)
H2O: ±2 ppm
H2: ±(LDL+5%)
CO: ±(LDL+3%)
CO2: ±(LDL+3%)
CH4: ±(LDL+3%)
C2H2: ±(LDL+3%)
C2H4: ±(LDL+3%)
C2H6: ±(LDL+3%)
O2: ±(LDL+10%)
N2: ±(LDL+15%)
H2O: ±2 ppm
Methane, ethane, ethylene, CO, CO2: ±10 ppm or 10% of reading
Acetylene: ±2 ppm or 10% of reading
Hydrogen: ±25 ppm or 20% of reading
Not available±5%, varies by gas measuredC2H4: ±10 ppm or 10% of reading
C2H2: ±2 ppm or 10% of reading
CO: ±10 ppm or 10% of reading
H2: ±25 ppm or 20% of reading
CxHx except C2H2: ±10 ppm or 10% of reading
C2H2: ±2 ppm or 10% of reading
CO, CO2: ±10 ppm or 10% of reading
H2: ±25 ppm or 20% of reading
CxHx except C2H2: ±10 ppm or 10% of reading
C2H2: ±2 ppm or 10% of reading
CO, CO2: ±10 ppm or 10% of reading
H2: ±25 ppm or 20% of reading
H2: ±5 ppm or 10% of reading
CH4: ±20 ppm or 10% of reading
C2H4: ±5 ppm or 5% of reading
C2H2: ±3 ppm or 5% of reading
CO: ±10 ppm or 10% of reading
±5% or ±LDL, whichever is greater±5%, varies by gas measured
Repeatability2H2: ±(LDL+5%)
CO: ±(LDL+5%)
CH4: ±(LDL+5%)
C2H2: ±(LDL+5%)
C2H4: ±(LDL+5%)
H2O: ±3 ppm
H2: ±(LDL+5%)
CO: ±(LDL+5%)
CO2: ±(LDL+5%)
CH4: ±(LDL+5%)
C2H2: ±(LDL+5%)
C2H4: ±(LDL+5%)
C2H6: ±(LDL+5%)
O2: ±(LDL+15%)
N2: ±(LDL+15%)
H2O: ±3 ppm
H2: ±(LDL+10%)
CO: ±(LDL+10%)
CO2: ±(LDL+10%)
CH4: ±(LDL+10%)
C2H2: ±(LDL+10%)
C2H4: ±(LDL+10%)
C2H6: ±(LDL+10%)
O2: ±(LDL+15%)
N2: ±(LDL+20%)
H2O: ±3 ppm
Methane, ethane, ethylene, CO, CO2: ±10 ppm or 5% of reading
Acetylene: ±1 ppm or 10% of reading
Hydrogen: ±15 ppm or 10% of reading
Not available<1%, varies by gasNot availableNot availableNot availableH2, CH4 and CO: 10% or LDL
C2H4 and C2H2: 5% or LDL
over 10 measurements
1% over 10 measurementsHydrogen: ±10%
All other gases: ±0.5%
Power requirements100–240 VAC +10%
100–220 VDC +10%
50/60 Hz
100–240 VAC +10%
100–220 VDC +10%
50/60 Hz
100–240 VAC −15% +10%, 50–60 Hz, 1 phase, 520 VA. Test report available for 240 VAC +15%100–240 VAC, 50/60 Hz ±10%90–250 VAC, 47/63 Hz115 VAC or 230 VAC ±15%, 50/60 Hz88–276 VAC, 50/60 Hz, option for 88–390 VDC88–276 VAC, 50/60 Hz, option for 88–390 VDC88–276 VAC, 50/60 Hz, option for 88–390 VDC90–250 VAC, 47/63 Hz
110–220 VDC
90–250 VAC, 47/63 Hz
110–220 VDC
100–240 VAC, 50/60 Hz
Gas extraction methodLow velocity pump continuously circulates oil past gas-permeable membrane tubesLow velocity pump continuously circulates oil past gas-permeable membrane tubesLow velocity pump continuously circulates oil past gas-permeable membrane tubesPatented vacuum gas extraction driven by magnetic gear pump, drawing a sample every 1–1.5 hoursOil pump turns on as needed to draw samples, head space gas extractionGas-permeable nanotubes. Pump runs continuouslyHead spaceHead spaceHead spaceOil pump turns on as needed to draw samples, head space gas extractionOil pump turns on as needed to draw samples, head space gas extractionPassive equilibrium through gas-permeable capillary tube
  1. Calculation based on oxygen measure.
  2. Accuracy noted is the accuracy of the detectors during the calibration process. Dissolved gas in liquid measurement accuracy may also be affected by sampling and/or fluid type. Consult with the manufacturer of the DGA monitor for further details.

Specifications subject to change without notice. Last updated August 5, 2025.