Circuit Breaker Monitoring Systems - Dynamic Ratings

Circuit Breaker Monitoring Systems Comparison Chart

Choosing the right circuit breaker monitoring system starts with understanding how the options compare. The chart below provides a side-by-side look at the Dynamic Ratings Breaker Performance Monitor alongside other systems on the market, outlining the key features, measured parameters, communication protocols, and sensor inputs supported by each. Use it to see how the solutions stack up and identify which one best fits your application, from basic condition monitoring to comprehensive diagnostics and integration with your existing substation or SCADA infrastructure.

Download PDF

Supported Not supported

Circuit breaker monitoring systems comparison
FeatureDynamic Ratings BPMHitachiIncon Optimizer 2Incon Optimizer 3GE CB Watch 3Qualitrol QBCM
General features
LEDs813173103
Alarm relays2 Form C
1 Form A
2, problem and caution2 Form C
1 Form A
1 Form C2 Form C, 16 Form A (optional module)3, undefined configuration
Sampling rate128 samples/cycle3.33 kHz; duration of 150 ms32 samples/cycle32 samples/cycle0.4 ms32 / 64 / 128 samples per cycle
Operating range-40 to +85°C with option for -50°C-40 to +70°C-40 to +65°C-40 to +65°C-40 to +55°C with option for -50°C-40 to +75°C
Humidity95% non-condensingNot stated85% non-condensing95% non-condensingNot stated97% non-condensing
Supply voltage88 to 276 VAC
88 to 288 VDC
48, 125 and 250 VDC85 to 264 VAC
110 to 370 VDC
90 to 264 VAC
110 to 250 VDC
150 to 240 VAC
150 to 250 VDC
-30 to +15%
100 to 240 VAC
125 to 250 VDC
User interfaceYesYes, Desktop applicationYesYesYes, Integrated webserverPC-based interface
Dimensions9.77 × 5 × 5.62″ ganged breaker
14.75 × 5 × 5.62″ IPO
11.5 × 3.47 × 6.25″8.69 × 5.63 × 3″11.13 × 5.63 × 2.63″6.5 × 9.4″15 × 5.5 × 2.75/3.5/4.5″
Measured parameters
Gas pressure / densityYesYesAnalog/digitalAnalog/digitalYesYes
Gas trendingYesYesYesNoYesYes
Gas dew pointYesNoNoYesNoYes
Contact wearWaveform analysisAux contactsAux contactsAux contactsAux contact or travel sensorNot stated
Arc timeWaveform analysisAux contactsAux contactsAux contactsOptional (aux contacts)Aux contacts
Restrike detectionWaveform analysisAux contactsAux contactsAux contactsNoAux contacts
Load currentSplit core CT with voltage outputSplit core CT with voltage outputSplit core CT with voltage outputSplit core CT with voltage outputOptionalSplit core CT with voltage output
Open timeWaveform analysisAux contactsAux contactsSplit core CT with voltage outputOptionalAux contacts
Close timeWaveform analysisAux contactsAux contactsSplit core CT with voltage outputOptionalAux contacts
Trip coil signatureWaveform captureNoNoTrip signature monitor neededOptionalAux contacts
Waveform comparisonYesYesNoTrip signature monitor neededNoYes
Timing determinationWaveform analysisWaveform analysisAux contactsAux contactsOptional (aux contacts / travel sensor)Timing transducer
Trip coil statusSplit core CTPulsed voltageNoTrip signature monitor neededOptionalSplit core CT
Close coil statusSplit core CTPulsed voltageNoTrip signature monitor neededOptionalSplit core CT
Charging motor run timeDirect inputTransducerNoTransducer requiredOptionalDirect input
Charging motor startsDirect inputTransducerNoTransducer requiredOptionalDirect input
Number of starts / time periodDirect inputYesNoTransducer requiredOptionalDirect input
Charging motor currentSplit core CTNoNoTransducer requiredOptionalSplit core CT
AC phase lossDirect input up to 240 VAC
Transducer above 240 VAC
TransducerNo4–20 mA transducerOptionalNot stated
Non-controlled cabinet heatersDirect inputTransducerNoAuxiliary unitOptionalNot stated
T-stat controlled cabinet heatersDirect inputTransducerNoAuxiliary unitOptionalNot stated
Tank heatersDirect inputTransducerNoAuxiliary unitOptionalYes
Cabinet temperatureRTDYesNoYesOptionalNot stated
Ambient temperatureRTDNot statedNot statedYesOptionalNot stated
Position of main contactsAux contactsAux contactsAux contactsAux contactsAux contacts / travel sensorAux contacts
Last operation dateSoftwareSoftwareSoftwareSoftwareYesSoftware
Operation countAux contactsSoftwareSoftwareSoftwareYesSoftware
Fault countSoftwareSoftwareSoftwareSoftwareNoSoftware
Communications
Ethernet (copper, fiber)YesOptionalYesYesYesYes
Serial (RS485, RS232, fiber)YesYesYesYesNoYes
Communication protocolsModbus, DNP, IEC 61850Modbus, DNPModbus, DNPModbus, DNPModbus, DNP, IEC 61850Modbus, DNP, IEC 61850
Sensor inputs
TemperatureCabinets, mechanism, tanksCabinets, tanksNot statedCabinets, tanksCabinets, tanksNot stated
SF6 gasYesYesYesYesYesYes
Load currentYesYesYesYesOptionalYes
Coil signatureYesNoNoTrip signature monitor neededYesYes
Coil monitoringYesPulsed currentNoTrip signature monitor neededYesYes
AC & DC power monitoringYesNoNo4–20 mA transducerOptionalYes
Auxiliary switchesYesYesYesYesOptionalYes

Specifications subject to change without notice. Last updated August 5, 2025.