DGA Comparison Chart - Key Gas - Dynamic Ratings

DGA Comparison Chart: Key Gas

How industry leading hydrogen and moisture monitors compare on gases monitored, installation and maintenance and system specifications. Dynamic Ratings supports communication to all major DGA monitors. We recognize that DGA monitors have different advantages and no one product would be optimal for all customers.

Download PDF

Compare monitors

Select two or more monitors to compare them side by side. All monitors are shown until you make a selection.Showing only the monitors you selected.

SupportedBlank: not supported or not listed

DGA comparison chart, key gas
FeatureDynamic RatingsH2Dynamic RatingsH2 + MoistureDobleCalisto 1DobleCalisto 2VaisalaMHT410General ElectricHydran M2General ElectricHydran 201TiServeron®TM1MTE Meter Test EquipmentHydrocal 1001+MTE Meter Test EquipmentHydrocal 1003MR/MESSKO®Msense® x2.5HitachiCoreSenseMeggerInsuLogix® G2
Gases monitored
Hydrogen H2YesYesYesYesYesNoNoYesNoYesYesYesYes
Composite gas sensorNoNoNoNoNoYesYesNoYesNoNoNoNo
Carbon monoxide CONoNoNoYesNoNoNoNoNoYesYesNoNo
Acetylene C2H2NoNoNoNoNoNoNoNoNoNoNoNoYes
Other information
MoistureNoYesYesYesYesYesYesNoYesYesYesYesYes
TemperatureNoYesNoNoYesNoNoYesNoNoNoNoYes
Fluid compatibilityHeadspace, mineral oil, silicone, natural & synthetic estersMineral oil, silicone, natural & synthetic esterMineral oil, silicone and natural & synthetic estersMineral oil, silicone and natural & synthetic estersMineral oil, silicone, natural & synthetic estersMineral oil, silicone and natural estersMineral oil, silicone and natural estersMineral oilMineral oil, silicone and natural estersMineral oil, silicone and natural estersMineral oilMineral oil and natural estersMineral oil and natural esters
Additional advantages when used with Dynamic Ratings
Dynamic Ratings certified to install and serviceYesYesYesYesYesNoNoNoNoNoNoNoNo
Single point support from Dynamic RatingsAvailableAvailableAvailableAvailableAvailableNoNoNoNoNoNoNoNo
Installation and maintenance
Installation mounting (length × width × depth)1.56 × 1.56 × 5.94 in
Screw onto valve
19.4 × 8.8 × 6.7 mm (7.63 × 3.47 × 2.65 in)
Screw onto valve
483 × 381 × 325 mm (19 × 15 × 12.8 in), 22.7 kg (50 lb), connected to separate inlet and outlet transformer valves483 × 381 × 325 mm (19 × 15 × 12.8 in), 22.7 kg (50 lb), connected to separate inlet and outlet transformer valvesScrew onto ball valve, push sensor through valve and tighten. Electrical clearance must be considered.Fits on 1.5 in minimum, open bore ball or gate valveFits on 1.5 in minimum, open bore ball or gate valveFits on 1.5 in minimum, open bore ball or gate valve224 × 195 × 218 mm (8.8 × 7.7 × 8.6 in), fits on 1.5 in bore ball or gate valve with NPT or ISO 228 thread224 × 195 × 218 mm (8.8 × 7.7 × 8.6 in), fits on 1.5 in bore ball or gate valve with NPT or ISO 228 threadScrew onto ball valve, push sensor through valve and tighten. Electrical clearance must be considered.Fits on 1.5 in minimum, open bore ball or gate valve227 × 229 × 333 mm (9 × 8.9 × 13.1 in), fits on 1.5 in minimum bore ball or gate valve
Recommended maintenance timelineNo maintenance requiredNo maintenance required4 years4 yearsNo maintenance requiredNo maintenance requiredNo maintenance required“No scheduled maintenance due to no membrane, no sensor replacement, and no consumables or gases”No maintenance requiredNo maintenance requiredNot availableNo maintenance requiredNo maintenance required
Warranty36 months36 months30 months30 months60 months18 months18 months24 months24 months24 monthsNot available36 months24 months
System description
Type of technologyHydrogen-specific semiconductor sensor immersed directly in the oil or headspaceHydrogen-specific semiconductor sensor immersed directly in the oil, able to take temperature, moisture and pressure readingsMembrane + TCDMembrane + TCDHydrogen-specific semiconductor sensor immersed directly in the oilMembrane + fuel cellMembrane + fuel cellHydrogen-specific semiconductor sensor immersed directly in the oilFuel cell sensorH2: SiO2 solid state sensor
CO: fuel cell sensor
Capillary semiconductor sensors, piezoelectric actuatorsSolid state sensor in oilC2H2: tunable diode laser spectrometer (TDLS)
H2: thermal conductivity detector (TCD)
Calibration verificationSelf diagnostics, no calibration requiredSelf diagnostics, no calibration requiredNot availableNot availableSelf diagnosticsSelf diagnostics every 15 daysSelf diagnostics every 15 daysOnce every 24 hours for 2 hoursDGA adjustment toolDGA adjustment toolAmbient airSelf diagnostics every 12 hoursSelf diagnostics, no calibration required
Accuracy1±20% of reading or ±25 ppm, whichever is greater±20% of reading or ±25 ppm, whichever is greater±5%H2: ±5%
CO: ±15%
±20% or ±25 ppm±10%, ±25 ppm±10%, ±25 ppm±15% or ±20 ppm±20 ppm or 15% of readingH2: ±25 ppm or 15% of reading
CO: ±25 ppm or 20% of reading
±10% or ±20 ppm±20%, ±25 ppmH2: ±25 ppm or 15% of reading
C2H2: ±0.5 ppm or 15% of reading
Repeatability1±10% or ±15 ppm±10% or ±25 ppm±3%H2: ±3%
CO: ±10%
±10% or ±10 ppm±5% or ±5%±5% or ±5%±5% or ±10 ppmNot availableNot available±5% or ±10 ppm±10%H2: ±10%
C2H2: ±14%
Power requirements12–48 VDC, 10 W12–30 VDC, 12 W100–240 VAC +10%
100–220 VDC +10%
50/60 Hz
100–240 VAC +10%
100–220 VDC +10%
50/60 Hz
15–30 VDC, 24 VAC (±15%)90–132 VAC or 180–264 VAC, 47/63 Hz100/115/200/230 VAC, 50/60 Hz100–240 VAC, 50/60 Hz88–276 VAC, 50/60 Hz
Option for 88–390 VDC
88–276 VAC, 50/60 Hz
Option for 88–390 VDC
95–280 VAC, 50/60 Hz
95–280 VDC
100–240 VAC, 50/60 HzAC: 90–264 VAC, 47–63 Hz
DC: 105–370 VDC, 120 W
Gas extraction methodSensors in direct contact with representative oil in the transformerSensors in direct contact with representative oil in the transformerLow velocity pump continuously circulates oil past gas-permeable membrane tubesLow velocity pump continuously circulates oil past gas-permeable membrane tubesSensors in direct contact with representative oil in the transformerInduced convective flow over membrane surfaceInduced convective flow over membrane surfaceSensor in direct contact with representative oil in the transformerInduced convective flow over membrane surfaceInduced convective flow over membrane surfaceTwo micropumps provide oil exchange between main body and gas extraction capillary tubesNo gas extraction. Induced convective flow over solid state sensor in oilInduced convective flow over gas-permeable membrane surface
  1. Accuracy noted is the accuracy of the detectors during the calibration process. Dissolved gas in liquid measurement accuracy may also be affected by sampling and/or fluid type. Consult with the manufacturer of the DGA monitor for further details.

Specifications subject to change without notice. Last updated August 5, 2025.