Switchgear and Cables

Industry data shows that switchgear has the highest failure rates commonly found in a facilities power distribution systems and that an average outage is 261 hours.
95% of forced outages in switchgear are attributed to failures of the insulation system.
Traditional maintenance programs, which are outage based, rarely include inspections of the main bus. Continuous monitoring of partial discharge (PD) activity, provides the means to detect pending insulation failures that are not present in traditional maintenance practices.
| IEEE Standard 493-1997 All Industry Equipment Type |
Failure Rate/Year |
Avg. Hours/Outage |
Avg. Downtime Hours/Year |
| Switchgear - Bus Only7 Sections | 0.0119 | 261 | 21.7413 |
| Large Power Transformers | 0.013 | 1076 | 13.988 |
| MV Synchronous Motors | 0.0318 | 175 | 5.565 |
| MV Induction Motors | 0.0404 | 76 | 3.0704 |
| Cables (Below Grade) - 3000 feet | 0.00613 | 53 | 0.97467 |
| Cable Terminators (3) | 0.000814 | 284 | 0.693528 |
| Small Power Transforers | 0.0025 | 217 | 0.5425 |
| MV Circuit Breakers | 0.0064 | 89.3 | 0.57152 |
| Bus Duct - 30 feet | 0.0038 | 128 | 0.4864 |

The key failure components of cables are the splices and terminations. 9 out of 10 failures will occur at these locations.
The same monitor used for switchgear can also provides the capability to monitor medium voltage cables in the switchyard.

